1MC
X
OFF
X
ON
X
1MC
CNB
CNB
CNA
CNA
(*4)
CN4
(*3)
CN1
CN1
B1
B3
B2
X
24 VDC
1
2
OUTM1
(BKIR)
OUTM1
COM
XB
24 VDC
W
V
U
L1C
L2C
L1
L3
ALMCOM
/ALM3
4
ECAT
RT
NFB
12
34
E
NF
1MC
PL
LM
IN
OUT
Main circuit
power supply
Regeneration
resistor (*5)
Main circuit contactor (*1)
Single-phase 100 to 120 VAC, 50/60Hz: R88D-KN

L-ECT-L
Single-phase 200 to 240 VAC, 50/60Hz: R88D-KN

H-ECT-L
Ground to
100 Ω or less
Ground to
100 Ω or less
External encoder
cables
Power cables (*2)
*1. A recommended product is listed in 4-3, Wiring Confirming
to EMC Directives.
*2. Do not use shielded cables for power cables.
*3.
Recommended relay: MY relay by OMRON (24 VDC 2A)
Select one that matches the ratings of the brake etc. to be used.
*4. Models with a built-in Regeneration Resistor
(KN04L-ECT-L, KN08H-ECT-L, KN10H-ECT-L, and
KN15H-ECT-L) have B2 and B3 shorted. When the
amount of regeneration is large, remove the connection
between B2 and B3 and connect the Regeneration
Resistor between B1 and B2.
*5
There is no Internal Regeneration Resistor for KN01L-ECT-L,
KN02L-ECT-L, and KN01H- ECT-L to KN04H-ECT-L. When
the amount of regeneration is large, connect the necessary
Regeneration Resistor between B1 and B2.
Motor
coil unit
Surge suppressor (*1)
Servo error display
G5-series AC Servo Drive
Reactor
User-side
control
device
Noise filter (*1)
External encoder
External sensor, etc.
General-purpose
inputs 1 to 8