1 SERVICE INFORMATION
Notice of Address setting for NEW Duct / NEW Outdoor Unit.
The new Duct Type / New Outdoor models are possible to have address setting for twin control by automatic when main
power supply is switched on.
(Manual address setting is also possible by using Dip switch on Indoor unit P.C. board.) However,
this address setting is only
possible when made proper wiring connection and also Indoor unit should be original virgin unit
.
1.1. Example of trouble at test operation
If found out as following phenomenon at test operation on site, it may have possibility of wrong address setting.
Therefore, please ensure of the address setting.
1. LCD display of wired remote control had not illuminate although the main power supply switch is ‘on’.
2. LCD display had indicated as normal illumination when power supply switch is ‘on’, however outdoor unit cannot be operated.
(But, it is necessary to take 3 to 5 minutes for outdoor unit to start from the timing of remote control ON/OFF switch is ‘on’.)
3. P.C. board had memorized wrong setting information.
a. If main power supply is switched ‘on’ with the wrong connection.
b. When changing the connection or combination of units due to re-installation etc.
When changing the system from twin control to normal one to one system.
When making the replacement of units as master and slave etc.
1.2. Caution of test operation
Do not touch the remote control switch and do not change any wirings for one minute when the main power supply switch is ‘on’.
(Because the unit is having automatic address setting during the first one minute.)
1.3. Caution during automatic address setting
When main power supply switch is ‘on’, the P.C. board will automatically memorized the connecting system.
Consequently, when initial power supply is ‘on’, there will not be interchangeability of units even of the same type and same
capacity unit. Therefore unable to connect the unit to another system.
1.4. Operation range
The applicable voltage range for each unit is given in “the following table”. The working voltage among the three phases must be
balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the
rated voltage.
1.4.1. Power Supply
Model
CU-
Unit Main Power Applicable Voltage
Phase, Volts Hz Maximum Minimum
B24DBE5
B28DBE5
B34DBE5
1~220 50 242 198
1~230 50 253 207
1~240 50 264 216
B28DBE8
B34DBE8
B43DBE8
B50DBE8
3N~380 50 418 342
3N~400 50 440 360
3N~415 50 457 374
1.4.2. Indoor and Outdoor Temperature
Model 50Hz ... B24DBE5, B28DBE5, B28DBE8, B34DBE5, B34DBE8, B43DBE8, B50DBE8
Operating Hz Indoor Temp. (D.B./W.B.) (°C) Outdoor Temp. (D.B./W.B.) (°C)
Maximum Minimum Maximum Minimum
Cooling 50 32/23 21/15 43/- -10/-
Heating 50 27/- 16/- 24/18 -10/-
3

Table of Contents

Other manuals for Panasonic CS-F43DD2E5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-F43DD2E5 and is the answer not in the manual?

Panasonic CS-F43DD2E5 Specifications

General IconGeneral
BrandPanasonic
ModelCS-F43DD2E5
CategoryAir Conditioner
LanguageEnglish

Related product manuals