12.3. During group control operation
System example
1. The main power is turned on while the transmission wires between the indoor units are not connected.
(open circuit at section A or B or C)
Symptom
Operation of indoor unit No.1 and No.3 is possible.
However "check" flashes in the remote control display for 3-5 minutes after main power is turned on.
Remote control unit : "check" flashes
Error code : F30-01 (indoor capacity error)
Indoor unit : LED1 on P.C.B flashes
Outdoor unit : LED6, 7 on P.C.B flashes
2. The main power is turned on while the remote control connection wire is not connected.
(open circuit at section D)
Symptom
Nothing abnormal appears on the remote control display.
Operation of indoor unit No.1 and No.2 is possible.
However indoor unit No.3 cannot be operated.
Remedy
1. Turn off the main power.
2. Connect the disconnected wire correctly.
3. Turn on the main power.
4. After 1 minute, start the operation using the remote control.
(Indoor unit operation will start according to the remote control setting.)
(Outdoor unit operation will start after 3-5 minutes.)
89

Table of Contents

Other manuals for Panasonic CS-F43DD2E5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-F43DD2E5 and is the answer not in the manual?

Panasonic CS-F43DD2E5 Specifications

General IconGeneral
BrandPanasonic
ModelCS-F43DD2E5
CategoryAir Conditioner
LanguageEnglish

Related product manuals