EasyManuals Logo
Home>Pulsar>Measuring Instruments>ULTRA Series

Pulsar ULTRA Series User Manual

Pulsar ULTRA Series
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
Page 12
P047 Outside Count
This parameter determines the number of processing cycles, or transducer ‘shots’,
that any valid echo must be seen outside of the gate before the gate will move and
allow the new echo to be processed. This will prevent any unwanted update, or
false readings being given due to the intermittent appearance of echoes from
devices such as scrapers.
Values Min = 1
Max = 5000
P883 Gate Expand (Available in Stability Menu under 1997)
This parameter is closely associated with the Outside Count as part of the
Damping parameters designed to make the reading more stable. When the Outside
Count has expired and the Gate is moving towards a new target then it expands at
a rate of 0.1m after every cycle.
Values Min = 0
Max = 99.99
Default = 10
Default = 0.1m/min

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar ULTRA Series and is the answer not in the manual?

Pulsar ULTRA Series Specifications

General IconGeneral
BrandPulsar
ModelULTRA Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals