EasyManuals Logo
Home>Rational>Oven>LM1 Series

Rational LM1 Series User Manual

Rational LM1 Series
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
11 | Exhaust gas connection on gas units
78 / 92 80.06.070_iCombi Pro-iCombi Classic_IM_V01_en-GB
Requirements for unit size 6-2/1 GN up to 20-2/1 GN
n
Type B23 exhaust air connection for these unit sizes corresponds to a
room air-dependent gas furnace with fans in front of burners without flow
guards and total rated load in installation space greater than 14 kW.
n
A clearance of 400 mm [15.75 inches] must be kept between the flue
pipes of the unit and the grease filters of the exhaust hood/ventilation
ceiling in order to prevent a risk of fire in the fat filter.
n
An ascending flow socket is not necessary.
n
Exhaust gases must be directed outside through kitchen ventilation sys-
tems. Type A gas units first emit exhaust gases into the room, and must be
promptly extracted via the kitchen ventilation system.
n
Monitor the exhaust vent to ensure that gas is only fed to the burners
when extraction is ensured.
11.3 Type B13 exhaust gas connection
NOTICE
Installation with a non-original flow guard
In order to prevent damage to the unit, use an original flow guard for a type
13 exhaust gas connection.
Requirements
n
Type B13 exhaust air connection corresponds to a room air-dependent
gas unit with fans in front of burners with a flow guard.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rational LM1 Series and is the answer not in the manual?

Rational LM1 Series Specifications

General IconGeneral
BrandRational
ModelLM1 Series
CategoryOven
LanguageEnglish

Related product manuals