EasyManuals Logo
Home>REPLIGEN>Laboratory Equipment>XCell ATF Series

REPLIGEN XCell ATF Series User Manual

REPLIGEN XCell ATF Series
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #110 background imageLoading...
Page #110 background image
XCell
TM
ATF System with C410:V4B Controller User Guide
106
Only one input loop shall be calibrated at a time. Each loop shall be calibrated in its entirety by
itself, without enabling (or initiating) the calibration of another loop.
The process of calibration is a 2-point linear scaling process, where a technician first confirms all
required utilities, external pressure gauge and loop wiring is connected. The following steps are
performed:
1) An enable bit is momentarily asserted. Controller is enabled in calibration mode for a
particular analog input.
2) Pneumatic devices are set to produce a minimum setting. The pressure in the system
approaches the minimum value commanded. Pressure gauge reading is allowed to
stabilize.
3) The pressure gauge reading is provided to the controller. A minimum capture bit is
momentarily asserted.
4) Pneumatic devices are set to produce a maximum setting. The value on the pressure
gauge is allowed to stabilize.
5) The pressure gauge reading is provided to the controller. A maximum capture bit is
momentarily asserted.
6) Once both minimum and maximum points are captured, the linear scaling calculation
can be performed by the PLC. This calculation is initiated by setting an accept bit
(momentarily asserted). Controller performs the linear scaling calculation and resets
the controller’s internal calibration enable bit.
Calibration Example
Technician calibrates the P2 pressure sensor.
1) Assert enable bit:
a. Set P2_Cal_Enable (input command bit) = 1 until P2_Cal_Enable (output
response bit) is set (= 1) and is received. When true…
b. Reset P2_Cal_Enable = 0.
c. Controller is enabled in calibration mode for P2 analog input.
2) Pneumatic devices are set to produce a minimum setting. (PV2=100%, PRV2=-5.00 PSI,
Solenoid=0 [vacuum])
a. While “SendingDataPage” is still equal to 3…
b. Set PV2_SP (input) = 100 Confirmed by examining DL_PV2 (output)
c. Set PRV2_SP (input) = -5 Confirmed by examining DL_PRV2 (output)
d. Reset Force_Solenoid (input) = 0 Confirmed by examining Solenoid_Forced
(output)
e. The pressure in the system approaches the minimum value commanded.
Pressure gauge reading is allowed to stabilize.
Note: P2_PV andPRV2_PV should be very near the value on the external pressure gauge.
3) Pressure gauge reading is provided to the controller.
a. Programmer provides a data entry location for technician to enter the pressure
value.
b. Set P2_P1_EU = the pressure value from the data entry location.
c. Set P2_P1_Capture = 1 until P2_P1_Captured bit is received. When true…

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the REPLIGEN XCell ATF Series and is the answer not in the manual?

REPLIGEN XCell ATF Series Specifications

General IconGeneral
BrandREPLIGEN
ModelXCell ATF Series
CategoryLaboratory Equipment
LanguageEnglish

Related product manuals