4 x Parameter settings
43
BA ROTEX HPSU compact 2 - 04/2011
4.2.3 Overview of factory-set parameter settings
Code 1
Code 2
Parameter name
Default factory settings
Value Range
Increment
Unit
0 Access authority
00 Authorisation level 3 2 - 3 1
1 Weather-dependent set value regulation
00 Lowest ambient temperature (Lo_A) -10 -20 - 5 1 °C
01 Highest ambient temperature (Hi_A) 15 10 - 20 1 °C
02 Target value at lowest ambient temperature 40 25 - 55 1 °C
03 Target value at highest ambient temperature 25 25 - 55 1 °C
2 Anti-legionella system
00 Operating interval FR every day
01 Status 1 0 - 1
02 Starting time 23:00 0:00 - 23:00 1:00 h
03 Target value 70 40 - 80 5 °C
04 Holding time 10 5 - 60 5 min.
3 Automatic restart
00 Status 0 0 - 1
4 Operation of optional additional heating and switch-off temperature for room heating
00 Status 1 0 - 1
01 Priority 0 0 - 2
02 Switch-off room heating in the summer 35 14 - 35 1 °C
03 Restricted operation of optional additional heater 3 0 - 3
04 (Not configurable, fixed value) 2
5 Bivalence temperature and priority temperature of room heating
00 Status bivalence temperature 1 0 - 1
01 Bivalence temperature 0 -15 - 35 1 °C
02 Priority for room heating 0 0 - 1
03 Priority temperature of room heating 0 -15 - 20 1 °C
04 Target value correction for hot water 10 0 - 20 1 °C
6 Hysteresis (DT) for water heating
00 Start 2 2 - 20 1
01 Stop 2 0 - 10 1
02 (Not configurable, fixed value)
(1
0—
7 Step length for hot water
00 Step length for hot water 0 0 - 4 1 °C
01 Hysteresisvalue booster heater (BOH) 2 2 - 20 1 °C
02 Status control on the basis of 2 target values Removed. Do not change the default value.
03 Control on the basis of 2 target values:
2. Target value for heating
Removed. Do not change the default value.
04 Control on the basis of 2 target values:
2. Target value for cooling
Removed. Do not change the default value.

Other manuals for Rotex HPSU compact (V5)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rotex HPSU compact (V5) and is the answer not in the manual?

Rotex HPSU compact (V5) Specifications

General IconGeneral
BrandRotex
ModelHPSU compact (V5)
CategoryHeat Pump
LanguageEnglish

Related product manuals