Installation
156/293 Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • 802-9081.9
Cutting the rubber sleeves to size
➭ With a knife, cut an opening into the rubber sleeve that fits the diameter of the cable.
Fig. 109: Cutting the rubber sleeves to size
Mounting the floor plates
➭ Push the rubber sleeve onto the cable T-plug.
➭ Connect the cable T-plug (see page 158, "Connecting cable T-plugs").
➭ Insert the rubber sleeve into the recess of the floor plate.
Fig. 110: Example for panel width 900 mm
INFORMATION
The rings in the rubber sleeves are not adjusted to the cable diameters, but serve only as rough
orientation.