802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11 71/293
Description
Fuse protection table for vacuum contactor (with HV HRC fuse-links make SIBA)
10.6 Fuse protection table for metering panel (with HV HRC fuse-links make SIBA)
Motor HV HRC fuse-link
Operating voltage Rated current Reference
dimension
Maximum permissible
normal current
Order No. SIBA Order No. of SIBA
extension tube
Part number of
Siemens
extension tube
U [kV] I
r
[A] e [mm] I [A]
3.3…7.2 40 292 30 30 098 13.40 34 006 01 02911500
50 442 38 30 108 53.50 --- ---
63 442 47 30 108 53.63 --- ---
80 442 60 30 108 53.80 --- ---
100 442 75 30 108 53,100 --- ---
125 442 85 30 109 53,125 --- ---
160 442 109 30 109 53,160 --- ---
200 442 130 30 110 54,200 --- ---
224 442 137 30 110 54,224 --- ---
250 442 157 30 110 54,250 --- ---
>7.2…12 40 442 29 30 101 13.40 --- ---
50 442 36 30 101 53.50 --- ---
63 442 45 30 101 53.63 --- ---
80 442 47 30 102 53.80 --- ---
100 442 59 30 102 53,100 --- ---
125 442 74 30 102 53,125 --- ---
160 442 90 30 103 53,160 --- ---
200 442 105 30 103 54,200 --- ---
12 125 442 78 30 469 13,125 --- ---
>12…23 40 442 23 30 006 13.40 --- ---
50 442 29 30 014 13.50 --- ---
63 442 36 30 014 43.63 --- ---
80 442 46 30 014 43.80 --- ---
100 442 54 30 022 43,100 --- ---
Voltage
transformer
HV HRC fuse-link
Operating voltage Rated current Reference
dimension
Order No. SIBA Order No. of SIBA
extension tube
Part number of
Siemens
extension tube
U [kV] I
r
[A] e [mm]
3.3 - 5.5 6.3 292 30 098 13.6,3 34 006 01 02911500
6.0 - 7.2 0.5 292 30 004 11.0,5 34 006 01 02911500
2.0 292 30 004 13.2 34 006 01 02911500
4.0 292 30 004 13.4 34 006 01 02911500
6.3 292 30 098 13.6,3 34 006 01 02911500
> 7.2 - 12 0.5 292 30 004 13.0,5 34 006 01 02911500
2.0 292 30 004 13.2 34 006 01 02911500
4.0 292 30 004 13.4 34 006 01 02911500
6.3 442 30 101 13.6,3 --- ---
> 12 - 23 0.5 442 30 006 11.0,5 --- ---
2.0 442 30 006 13.2 --- ---
4.0 442 30 006 13.4 --- ---
6.3 442 30 006 13.6,3 --- ---