802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11 189/293
Operation
19.4 Ready-for-service indicator
19.5 Circuit-breaker locking device for "feeder earthed"
The circuit-breaker locking device for "feeder earthed" is operated to lock a circuit-breaker
panel with earthed feeder and secure it against de-earthing.
The operated locking device can be padlocked.
As standard, the locking device can only be operated when the three-position disconnector is
in READY-TO-EARTH position and the circuit-breaker is in CLOSED position. Operating the
locking device in other switch positions is locked as standard.
Preconditions Three-position disconnector in "READY-TO-EARTH" position
Circuit-breaker in CLOSED position
Shackle diameter of the padlock: Min. 6 mm.
Actuating the locking
device
Push the lever of the locking device upwards.
Fig. 155: Circuit-breaker locking device
Fit and lock the padlock.
CAUTION
Internal arcing hazard and explosion hazard
Switching without service readiness can cause serious injury or property damage.
Check service readiness of the switchgear before performing any switching operation. The
pointer of the ready-for-service indicator must be in the green area.
If the pointer of the ready-for-service indicator is in the red area:
- All panel types except circuit-breaker panels: Do not operate the switchgear.
- Contact the Siemens Service Hotline.
Fig. 154: Ready-for-service indicator
Switchgear ready for service (green area)
Switchgear not ready for service (red area)
Pointer
NOTICE
Maloperation of the locking device
Can cause considerable property damage.
For a panel optionally equipped without interlocking between locking device and three-
position disconnector: If the circuit-breaker and the three-position disconnector are in
CLOSED position, do not operate the locking device.
If the locking device is operated, all electrical and mechanical opening commands (e.g.
protection tripping) are ineffective.
Operate the locking device only under the following conditions:
- Three-position disconnector switched to READY-TO-EARTH position.
- Circuit-breaker switched to CLOSED position.