802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11 235/293
Operation
Disconnector panel as of 2000 A: Disconnecting the feeder from the busbar
1
Initial situation
2
➭ Push the interrogation lever downwards and
hold it.
3
➭ Push the control gate to the left.
4
➭ Switch the three-position disconnector
to OPEN position (insert the operating
lever and turn 180° counter-clockwise).
5
➭ Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).