Service information
Mounting the interlock Carefully thread the interlocking into the operating mechanism. Insert the lug into the
driver at the top, and the tripping rocker into the slide .
Fasten bolts and (both M6x12 with hexalobular socket)
Tighten the rocker with the bolted joint .
Fix the cables again with 2 cable straps.
Refit the front cover of the panel.
Test proper functioning of the interlock according to the following table. All control
elements must be easy to operate.
Oil the bearing for the operating shaft. Shell Tellus Oil S2M32
Apply grease to the guide of the closing
spring.
Precondition: Closing spring charged.
WARNING: Do not reach into the
operating mechanism compartment
with your hands when the operating
springs are charged.
Isoflex Topas L32
Detail view Component Lubricants
Bolt, left side
Bolted joint
Lug
Tripping rocker
Slide
Cable strap (2x)
Bolt, right side