Siemens Desigo Touch and Web CM111029en_04
Building Technologies Compatibility & limitations – System limits 2014-08-15
2.5.4 Supported BACnet objects
Text # Name Type # Description
0 DEV 8 Device
1 AI 0 Analog input
2 AVAL_OP 2 Analog value for operation
3 AO 1 Analog output
4 AVAL 2 Analog value
6 BI 3 Binary input
7 BVAL_OP 5 Binary value for operation
8 BO 4 Binary output
9 BVAL 5 Binary value
10 BSCHED 17 Binary scheduler
11 MI 13 Multistate input
12 MVAL_OP 19 Multistate value for operation
13 MO 14 Multistate output
14 MVAL 19 Multistate value
15 MSCHED 17 Multistate scheduler
16 CLN 6 Calendar
18 TRNDLOG 20 Trend log
19 CI 24 Counter input
20 CMD_CTL 216 Command Control
21 PWR_CTL 216 Power Control
22 AI_RED 0 Analog input, reduced function
23 AO_RED 1 Analog output, reduced function
24 BI_RED 3 Binary input, reduced function
25 BO_RED 4 Binary output, reduced function
26 MI_RED 13 Multistate input, red.function
27 MO_RED 14 Multistate output, red.function
31 CI_ACC 23 Counter input, accumulated
35 SCHED 17 Schedule*
50 USRPRF 207 User profile
58 Block 201 Block**
69 CMN_ALM 214 Common alarm
70 DevInfo 217 Device information for alarming
* no analog scheduler
** Block types are Desigo-specific
Note
MSCHED
MSCHED can have 6 different states, and 10 for TREND.
If more states exist, only the first 6 or 10 are displayed.
USRPRF
– The PXG3.W100 web interface supports user profiles with access level
≥ Extended Operation, allowing for resetting and confirming alarms.
– Read/write access rights to the BACnet object level are not processed.