Siemens RDF302 Basic documentation CE1P3079en
Smart Infrastructure 2022-06-17
P09 P10
Cooling setpoint adjustable 25…40 °C
Heating setpoint adjustable 5…21 °C
Use control parameters P11 and P12 to adjust the Economy mode setpoints.
The heating setpoint is factory-set to 15 °C, and the cooling setpoint to 30 °C.
Use control parameters P65 and P66 to adjust the Protection mode setpoints.
The heating setpoint is factory-set to 8 °C (frost protection) and to OFF for cooling.
If a setpoint (Economy or Protection) is set to OFF, the thermostat does not control
the room temperature in the corresponding mode (heating or cooling).
This means no protective heating or cooling function and thus risk of frost in
heating mode or risk of over-temperature in cooling mode!
The Economy setpoints are accessible at the service level (P11, P12); the
Protection setpoints at the expert level (P65, P66).
3.3.2 Setting and adjusting setpoints
Room temperature setpoints can be
set during commissioning
adjusted during runtime
The source can be via
local HMI
a Modbus commissioning tool
a Modbus master unit
The thermostat stores the setpoints
in EEPROM in the form of parameters
The table below shows the interrelations:
Economy mode
Protection mode
Caution
Room temperature:
Comfort setpoint

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDF302/VB and is the answer not in the manual?

Siemens RDF302/VB Specifications

General IconGeneral
BrandSiemens
ModelRDF302/VB
CategoryThermostat
LanguageEnglish

Related product manuals