EasyManuals Logo
Home>Siemens>Thermostat>RDF302/VB

Siemens RDF302/VB User Manual

Siemens RDF302/VB
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
24 / 62
Siemens RDF302 Basic documentation CE1P3079en
Smart Infrastructure 2022-06-17
3.6.2 2-pipe fan coil unit
On 2-pipe applications, the thermostat controls a valve in heating / cooling mode
with changeover (automatically or manually), heating only, or cooling only. Cooling
only is factory-set (P01 = 1).
ON/OFF control
The diagrams below show the control sequence for 2-position control.
Heating mode
Cooling mode
½ SDH
1
0
½ SDH
w
Y
3076D01
TC]
V1
Y
½ SDC
1
0
½ SDC
w
3076D02
TC]
V1
T[°C] Room temperature
SDH Switching differential “Heating” (P30)
w Room temperature setpoint
SDC Switching differential “Cooling (P31)
V1 Control command “Valve” or “Compressor”
Modulating control: 3-position
The diagrams below show the control sequence for modulating PI control.
Heating mode
Cooling mode
XpH
100
0
w
Y [%]
3076D03
TC]
V1
XpC
Y [%]
100
0
w
3076D04
TC]
V1
T[°C] Room temperature
XpH Proportional band “Heating” (P30)
w Room temperature setpoint
XpC Proportional band “Cooling (P31)
V1 Control command “Valve”
The diagrams only show the PI thermostats proportional part.
Setting the sequence and the control outputs
Refer to sections 3.4 "Applications", 3.6.1 "Sequences", and 3.7 "Outputs".
Control sequence
ON/OFF output
Control sequence
modulating output
Note:

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RDF302/VB and is the answer not in the manual?

Siemens RDF302/VB Specifications

General IconGeneral
BrandSiemens
ModelRDF302/VB
CategoryThermostat
LanguageEnglish

Related product manuals