3.6.5 Chilled / heated ceiling and radiator applications
For chilled / heated ceiling and radiator,
• set the corresponding basic application
• disable the fan (P52)
The following applications are available:
Application for
chilled / heated ceiling, radiator
Chilled / heated ceiling with
changeover
Chilled / heated ceiling & el heater
(cooling only: disable el heater via
P13)
2-pipe and electric heater
El H + H ( \ \ )
El H + C ( \ / )
C ( / )
Chilled ceiling and radiator
3.6.6 Compressor applications
For compressor applications,
• set the corresponding basic application
• disable the fan (P52) or set the fan speed (P53)
The following applications are available:
Application for compressor
1-stage compressor
for heating or cooling
1-stage compressor and electric
heater
(for cooling only: disable electric
heater via P13)
2-pipe and electric heater
El H + H ( \ \ )
El H + C ( \ / )
C ( / )
1-stage compressor
for heating and cooling
• Minimum ON/OFF time: P48 / P49
• Fan operation: P52 (0 = disabled, 1 = enabled)
• Fan speed: P53 (1 = 1-speed, 2 = 3-speed)