Technical Specifications
5.2Failsafe Relay Specifications
d
The HI power supply is the same power supply for both AC and DC.
5.2 Failsafe Relay Specifications
Max Switching Volt-
age
240 VAC, 125 VDC
Rated Switching Cur-
rent
2 A @ 240 VAC, 0.15 A @ 125 VDC, 2 A @ 30 VDC
Maximum Switching
Capacity
150 W, 500 VA
5.3 Supported Networking Standards
Standard 10 Mbps Ports 100 Mbps
Ports
1000 Mbps
Ports
Description
IEEE 802.3
ü
10BaseT/10BaseFL
IEEE 802.3u
ü
100BaseTX/100BaseFX
IEEE 802.3x
ü ü ü
Flow Control
IEEE 802.3z
ü
1000BaseLX
IEEE 802.3ab
ü
1000BaseTx
IEEE 802.3ad
ü
Link Aggregation
IEEE 802.1D
ü ü ü
MAC Bridges
IEEE 802.1D
ü ü ü
Spanning Tree Protocol (STP)
IEEE 802.1p
ü ü ü
Class of Service (CoS)
IEEE 802.1Q
ü ü ü
VLAN (Virtual LAN) Tagging
IEEE 802.1w
ü ü ü
Rapid Spanning Tree Protocol
(RSTP)
IEEE 802.1x
ü ü ü
Port-Based Network Access Con-
trol
IEEE
802.1Q-2005
(former-
ly 802.1s)
ü ü ü
Multiple Spanning Tree Protocol
(MSTP)
5.4 Copper Ethernet Port Specifications
The following details the specifications for copper Ethernet ports that can be ordered
with the RUGGEDCOM RSG2100.
Note
• Maximum segment length is greatly dependent on factors such as fiber quality,
and the number of patches and splices. Consult a Siemens sales associate when
determining maximum segment distances.
32
RUGGEDCOM RSG2100
Installation Manual, 03/2020, C79000-G8976-1040-17