Certification
6.1.9RoHS
6.1.9 RoHS
This device is declared by Siemens AG to meet the requirements of the following Ro-
HS (Restriction of Hazardous Substances) directives for the restricted use of certain
hazardous substances in electrical and electronic equipment:
• China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic Informa-
tion Products
A copy of the Material Declaration is available online at https://support.indus-
try.siemens.com/cs/ww/en/view/109738831.
6.1.10 Other Approvals
This device meets the requirements of the following additional standards:
• IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
• IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
• IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Require-
ments
• EN 50121-4
Railway Applications – Electromagnetic Compatibility – Emission and Immunity
of the Signaling and Telecommunications Apparatus
6.2 EMC and Environmental Type Tests
The RUGGEDCOM RSG2100 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests per IEC 61850-3
Note
• In the case of an all fiber port configuration, this product meets all Class 2 re-
quirements. Otherwise, all Class 1 requirements are met for copper ports.
• If the unit contains copper ports, the IEC 1613 conformance is Class 1, during
which disturbance errors may occur but recovery is automatic.
RUGGEDCOM RSG2100
Installation Manual, 03/2020, C79000-G8976-1040-17
43