Certification
6.2EMC and Environmental Type Tests
• If the unit contains all fiber ports, the IEC 1613 conformance is Class 2, during
which no disturbance errors will occur.
Test Description Test Levels Severity Levels
Enclosure Contact ±8 kVIEC 61000-4-2 ESD
Enclosure Air ±15 kV
4
IEC 61000-4-3 Radiated RFI Enclosure Ports 20 V/m Note
a
Signal Ports ±4 kV @ 2.5 kHz Note
a
DC Power Ports
AC Power Ports
IEC 61000-4-4 Burst (Fast
Transient)
Earth Ground Ports
±4 kV 4
Signal Ports ±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
4
DC Power Ports ±2 kV Line-to-
Ground, ±1 kV
Line-to-Line
3
IEC 61000-4-5 Surge
AC Power Ports ±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
4
Signal Ports
DC Power Ports
AC Power Ports
IEC 61000-4-6 Induced (Con-
ducted) RFI
Earth Ground Ports
10 V 3
100 A/m
Continuous
IEC 61000-4-8 Magnetic Field Enclosure Ports
1000 A/m for 1 s
5
IEC 61000-4-11 Voltage Dips
and Interrupts
AC Power Ports 30% for 1 period
60% for 50 periods
100% for 5 periods
100% for
50 periods
Signal Ports
DC Power Ports
IEC 61000-4-12 Damped
Oscillatory
AC Power Ports
2.5 kV Common
1 kV Differential
Mode @1 MHz
3
Signal PortsIEC 61000-4-16 Mains Frequen-
cy Voltage
AC and DC
Power Ports
30 V Continuous
300 V for 1s
4
IEC 61000-4-17 Ripple on DC
Power Supply
DC Power Ports 10% 3
IEC 61000-4-18 Damped Os-
cillatory Wave
Slow Damped 2.5 kV Common
Mode on Pow-
er and Signal
1.0 kV Differential
Mode on Power
3
IEC 61000-4-29 Voltage Dips
and Interrupts
DC Power Ports 30% for 0.1 s
44
RUGGEDCOM RSG2100