Technical specifications
8.7 Technical specifications
Basic Panels 2nd Generation
112 Operating Instructions, 10/2016, A5E33293231-AB
Interfaces
KTP900 Basic
KTP1200 Basic
KTP1200 Basic DP
1 x RS 422/RS 485
-
Max. 12 Mbps
1 x Ethernet RJ45 10/100 Mbps -
USB 2.0
Yes
Supply voltage
KTP900 Basic
KTP1200 Basic
KTP1200 Basic DP
Rated voltage +24 V DC
Permitted voltage range
19.2 .. 28.8 V (20%, +20%)
Transients, maximum permitted 35 V (500 ms)
Time between two transients, minimum
50 s
Current
consumption
Typical
Approx. 230 mA
Approx. 510 mA
Approx. 550 mA
Constant current, maximum
Approx. 440 mA
Approx. 650 mA
Approx. 800 mA
Inrush current I
2
t
Approx. 0.2 A
2
s
Fuse, internal
Electronic
Miscellaneous
KTP900 Basic
KTP1200 Basic
KTP1200 Basic DP
Buffered real-time clock
1
,
can be synchronized
Yes
Acoustic feedback
Yes
1
Typical buffer time: 3 weeks

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC HMI KTP1200 Basic DP and is the answer not in the manual?

Siemens SIMATIC HMI KTP1200 Basic DP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC HMI KTP1200 Basic DP
CategoryControl Panel
LanguageEnglish

Related product manuals