Technical specifications
8.8 Interface description
Basic Panels 2nd Generation
114 Operating Instructions, 10/2016, A5E33293231-AB
8.8.3
PROFINET (LAN)
Name of interface on HMI device: PROFINET (LAN) X1
RJ45 plug connector
Pin
Assignment
1
Tx+
2
Tx
3
Rx+
4
n. c.
5
n. c.
6
Rx
7
n. c.
8
n. c.
Meaning of LEDs
There is no connection if both LEDs are off.
The green "Link" LED lights up as soon as there is a physical connection.
The yellow "Activity" LED lights up during the data transfer.
8.8.4
USB
Name of interface on HMI device: USB X60
USB socket
The following table shows the pin assignment of the USB port.
Pin
Assignment
1
+5 V DC, out, max. 500 mA
2
USB-DN
3
USB-DP
4
GND