3.1.4 Commissioning the expansion module PAC PROFINET (828D)
To communicate via PROFINET, the SENTRON SWITCHED ETHERNET PROFINET module
in combination with Sentron PAC3200/4200 must be parameterized differently.
1. Select SENTRON PAC "Settings" > "SWITCHED ETHERNET".
- OR -
Select SENTRON PAC "Settings" > "Expansion modules" > "MOD1" > "SWITCHED
ETHERNET".
2. Press "ENTER".
You obtain the following information in the subsequent window:
– Order number
– Serial number of the SENTRON SWITCHED ETHERNET PROFINET module
– Firmware version of the SENTRON SWITCHED ETHERNET PROFINET module
– The first character of the NameOfStation of the SENTRON SWITCHED ETHERNET
PROFINET module that can be a maximum of 26 characters
– IP-ADDR.:
The IP address of the module is displayed here.
3. Using the menu item "- ->", open the next window and obtain among other things the
information about the SUBNET address of the module.
Specifying/changing the device name
The device name can only be entered (it must be specified) using the powerconfig software
in the submenu "Expansion slot1".
● Sentron PAC3200: pac3200-pn22
● Sentron PAC4200: pac4200-pn21
The next time that the 828D boots, the 828D IO controller assigns the correct IP address to
the expansion module according to the device name:
● pac4200-pn21 --> 192.168.214.21
● pac3200-pn22 --> 192.168.214.22
3.2 Commissioning the PLC for SENTRON PAC
3.2.1 SINUMERIK 840D sl
3.2.1.1 Commissioning the PLC with PROFIBUS
PROFIBUS is commissioned with the PLC Toolbox 4.6 or higher.