28 T7 Number of operating hours in Temperature range 7 0to4.29E9 Hours
29 T8 Number of operating hours in Temperature range 8 0to4.29E9 Hours
30 T9 Number of operating hours in Temperature range 9 0to4.29E9 Hours
31 VENT1 Number of cycles pre--controlvalve 1 0to4.29E9 --
32 VENT2 Number of cycles pre--controlvalve 2 0to4.29E9 --
33 STORE Store current values as ”last maintenance”
(press increment key for 5 s) (Store)
-- --
Table 3-1 Overview diagnostic values
4.5.2 Meaning of the diagnostic values
Number of strokes
The actuator movements during operation are totaled and can be read
here as number of strokes. Unit: 100% stokes The value is written
every hour in a non--volatile memory. It can be reset to zero with the
increment key
.
Number of direction changes
Every change in direction leaving the dead zone is noted in the
controller and added to the number of changes of direction.
The value is written every hour in a non--volatile memory. It can be
reset to zero with the increment key
.
Fault counter
Every fault is noted in the controller and added to the number of fault
messages. The counter can be reset to zero with the increment key
.
Alarm counter 1
and
Alarm counter 2
Responses of alarm 1 and alarm 2 are counted with these two
counters. The prerequisite is the activation of the alarms with the
parameter “44.AFCT”. The counters can be reset to zero with the
increment key
.
Operating hours
The operating hours counter is updated every hour as soon as the
positioner has been supplied with electrical power.
1 STRKS
2 CHDIR
3 CNT
4 A1CNT
5 A2CNT
6 HOURS