Fused selection tables up to 690 V
5.2 Short-circuit protection: Contactor + 3RU2 thermal overload relay, type of coordination 1 and 2
Configuring SIRIUS Innovations
72 Configuration Manual, 04/2010, A8E56203880102-02
5.2 Short-circuit protection: Contactor + 3RU2 thermal overload relay,
type of coordination 1 and 2
Short-circuit protection up to 100 kA
Type of coordination 1 and 2
Table 5- 2 Fuse links according to IEC 60947 operating class gG,
(NH DIAZED, NEOZED; type 3NA, 5SB, 5SE)
Overload relay thermal Contactor Fuse links
1)
MLFB Setting range MLFB P [kW] Type of coordination
1
2)
Type of coordination
2
2)
Size S00
3RU2116-0AB0 0,11 ... 0,16 3RT2015-1.. 3 25 0,5
3RU2116-0BB0 0,14 ... 0,20 3RT2015-1.. 3 25 1
3RU2116-0CB0 0,18 ... 0,25 3RT2015-1.. 3 25 1
3RU2116-0DB0 0,22 ... 0,32 3RT2015-1.. 3 25 1,6
3RU2116-0EB0 0,28 ... 0,40 3RT2015-1.. 3 25 2
3RU2116-0FB0 0,35 ... 0,50 3RT2015-1.. 3 25 2
3RU2116-0GB0 0,45 ... 0,63 3RT2015-1.. 3 25 2
3RU2116-0HB0 0,55 ... 0,80 3RT2015-1.. 3 25 4
3RU2116-0JB0 0,70 ... 1,0 3RT2015-1.. 3 25 4
3RU2116-0KB0 0,90 ... 1,25 3RT2015-1.. 3 25 4
3RU2116-1AB0 1,10 ... 1,60 3RT2015-1.. 3 35 6
3RU2116-1BB0 1,4 ... 2,0 3RT2015-1.. 3 35 6
3RU2116-1CB0 1,8 ... 2,5 3RT2015-1.. 3 35 10
3RU2116-1DB0 2,2 -3,2 3RT2015-1.. 3 35 10
3RU2116-1EB0 2,8 ... 4,0 3RT2015-1.. 3 35 16
3RU2116-1FB0 3,5 ... 5,0 3RT2015-1.. 3 35 20
3RU2116-1GB0 4,5 ... 6,3 3RT2015-1.. 3 35 20
3RU2116-1HB0 5,5 ... 8,0 3RT2016-1.. 4 35 20
3RU2116-1JB0 7,0 ... 10 3RT2016-1.. 4 35 20
3RU2116-1KB0 9,0 ... 12,5 3RT2017-1.. 5,5 35 20
3RU2116-4AB0 11 ... 16 3RT2018-1.. 7,5 50 25