Fused selection tables up to 690 V
5.6 Short-circuit protection: Star-delta (wye-delta) contactor
Configuring SIRIUS Innovations
Configuration Manual, 04/2010, A8E56203880102-02
83
5.6 Short-circuit protection: Star-delta (wye-delta) contactor
Short-circuit protection with fuses for motor feeders with 3RU21
up to 690 V / 100 kA, type of coordination 1 and 2
Table 5- 12 Fuse links according to IEC 60947 operating class gG,
(NH DIAZED, NEOZED; type 3NA, 5SB, 5SE)
Contactor Fuse links
1)
Overload relay
Line and delta Star Type of coordination
2)
MLFB Setting range MLFB MLFB P [kW] 1 2
Size S00
3RU2116-0AB0 0,11 ... 0,16 3RT2015-1AP01 3RT2015-1AP01 3 25 0,5
3RU2116-0BB0 0,14 ... 0,20 3RT2015-1AP01 3RT2015-1AP01 3 25 1
3RU2116-0CB0 0,18 ... 0,25 3RT2015-1AP01 3RT2015-1AP01 3 25 1
3RU2116-0DB0 0,22 ... 0,32 3RT2015-1AP01 3RT2015-1AP01 3 25 1,6
3RU2116-0EB0 0,28 ... 0,40 3RT2015-1AP01 3RT2015-1AP01 3 25 2
3RU2116-0FB0 0,35 ... 0,50 3RT2015-1AP01 3RT2015-1AP01 3 25 2
3RU2116-0GB0 0,45 ... 0,63 3RT2015-1AP01 3RT2015-1AP01 3 25 2
3RU2116-0HB0 0,55 ... 0,80 3RT2015-1AP01 3RT2015-1AP01 3 25 4
3RU2116-0JB0 0,70 ... 1,0 3RT2015-1AP01 3RT2015-1AP01 3 25 4
3RU2116-0KB0 0,90 ... 1,25 3RT2015-1AP01 3RT2015-1AP01 3 35 4
3RU2116-1AB0 1,10 ... 1,60 3RT2015-1AP01 3RT2015-1AP01 3 35 6
3RU2116-1BB0 1,4 ... 2,0 3RT2015-1AP01 3RT2015-1AP01 3 35 6
3RU2116-1CB0 1,8 ... 2,5 3RT2015-1AP01 3RT2015-1AP01 3 35 10
3RU2116-1DB0 2,2 ... 3,2 3RT2015-1AP01 3RT2015-1AP01 3 35 10
3RU2116-1EB0 2,8 ... 4,0 3RT2015-1AP01 3RT2015-1AP01 3 35 16
3RU2116-1FB0 3,5 ... 5,0 3RT2015-1AP01 3RT2015-1AP01 3 35 20
3RU2116-1GB0 4,5 ... 6,3 3RT2015-1AP01 3RT2015-1AP01 3 35 20
3RU2116-1HB0 5,5 ... 8,0 3RT2015-1AP01 3RT2015-1AP01 4 35 20
3RU2116-1JB0 7,0 ... 10 3RT2015-1AP01 3RT2015-1AP01 4 35 20
3RU2116-1KB0 9,0 ... 12,5 3RT2015-1AP01 3RT2015-1AP01 5,5 35 20
3RU2116-4AB0 11 ... 16 3RT2017-1AP01 3RT2017-1AP01 7,5 50 25