SITOP PSU300S
Manual, 12.2016, C98130-A7587-A1-7-7629
51
6EP1433-2BA20 (24 V/5 A)
6EP1434-2BA20 (24 V/10 A)
6EP1436-2BA10 (24 V/20 A)
6EP1437-2BA20 (24 V/40 A)
Ambient temperature -25 ... 70 °C for natural convection (self convection)
Remark:
for 6EP1437-2BA20 with EZ 1: -10 … 70 °C
Tested according to:
• EN 60068-2-1 Cold
• EN 60068-2-2 Dry heat
• EN 60068-2-78 Humid heat, constant
• EN 60068-2-14 Temperature change
Transport and storage tempera-
ture
-40 ... 85 °C
Tests (packed for shipping) according to:
• EN 60068-2-1 Cold
• EN 60068-2-2 Dry heat
• EN 60068-2-30 Humidity heat, cyclic
Climatic class 3K3 according to EN 60721, 5 - 95 % no condensation
Mechanical stressing in operation
• Tested according to EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 - 8.4 Hz
2 g acceleration in the range 8.4 - 150 Hz
Comment:
for 6EP1437-2BA20 with EZ 1: 1.3 g acceleration in the range 8.4 - 150 Hz
• Tested according to EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms