ACC4100 Diesel Air Compressor Controller User Manual Page 20 of 52
8 CONFIGURATION PARAMETER RANGE AND DEFINITION
8.1 PARAMETER RANGE AND DEFINITION
Table 9 Parameter Setting Contents and Range List
0: Simplified Chinese 1: English
Set LCD backlight brightness;
Backlight is always on when delay is set to
0min.
Controller address for remote monitoring;
0: 2-bit Stop Bit
1: 1-bit Stop Bit (PC software settings)
It used for advanced parameter setting;
Caution! Default password is “1234”; It can be
changed by operator for purpose of preventing
others changing controller advanced
configuration.
If password is changed, please remember clearly.
If it is forgotten, please contact company service
person.
Users can calibrate date and time.
Independent password for maintenance.
Time for pre-heating plug to be energized
before starter is energized.
Time for fuel relay output every time
before starter is energized.
Time for starter to be energized every
time.
Waiting time before second energization
when engine fails to start.
During this time oil pressure low, temp.
high, under speed, under frequency, under
voltage, and charge alt failure alarms are
all inactive.
Time for engine idle running in start
process.