HGM6100LT Series Genset Controller User Manual Page 41 of 50
13 CONNECTIONS OF CONTROLLER WITH J1939 ENGINE
13.1 CUMMINS ISB/ISBE
Table 13 – Connector B
Set programmable output 1 as “Fuel
Output”.
Connect with starter coil directly.
Expand 30A relay, battery
voltage of 01, 07, 12, 13 is
supplied by relay.
ECU power;
Set programmable output 2 as “ECU
power”.
Table 14 – 9 Pins Connector
CAN communication shielding line
(connect to ECU terminal only).
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Engine type: Cummins ISB.
13.2 CUMMINS QSL9
Suitable for CM850 engine control module.
Table 15 – 50 Pins Connector
Set programmable output 1 as “Fuel
Output”.
Connect to starter coil directly.
Table 16 – 9 Pins Connector
CAN communication shielding line
(connect to ECU terminal only).
Using impedance 120Ω connecting line.
Using impedance 120Ω connecting line.
Engine type: Cummins-CM850.