HGM6100LT Series Genset Controller User Manual Page 45 of 50
13.9 DEUTZ EMR2
Table 26 F Connector
Terminals of controller
F connector
Remark
Programmable output 1
Expand 30A relay, battery
voltage of 14 is supplied by
relay. Fuse is 16A.
Set programmable output 1 as “Fuel
Output”.
Starting relay output
-
Connect to starter coil directly.
-
1
Connect to battery negative pole.
CAN_SCR
-
CAN communication shielding line.
CAN(H)
12
Using impedance 120Ω connecting line.
CAN(L)
13
Using impedance 120Ω connecting line.
Engine type: Volvo EDC4.
13.10 JOHN DEERE
Table 27 21 Pins Connector
Terminals of controller
21 pins connector
Remark
Programmable output 1
G, J
Set programmable output 1 as “Fuel
Output”.
Starting relay output
D
CAN_SCR
-
CAN communication shielding line.
CAN(H)
V
Using impedance 120Ω connecting line.
CAN(L)
U
Using impedance 120Ω connecting line.
Engine type: John Deere.
13.11 MTU MDEC
Suitable for MTU engines, 2000 series, 4000 series.
Table 28 X1 Connector
Terminals of controller
X1 connector
Remark
Programmable output 1
BE1
Set programmable output 1 as “Fuel
Output”.
Starting relay output
BE9
CAN_SCR
E
CAN communication shielding line
(connect to one terminal only).
CAN(H)
G
Using impedance 120Ω connecting line.
CAN(L)
F
Using impedance 120Ω connecting line.
Engine type: MTU-MDEC.