STATYS XS - IOMSTAXS1217-EN_04 - SOCOMEC
6.4. Conguration
Statys XS can be customised via USB or serial link using a dedicated software named XS Cong.
Please refer to the download section of www.socomec.com.
7. DRY CONTACTS AVAILABLE FOR CONFIGURATION
Event Code
1 Source A voltage abnormal Er03
2 Source B voltage abnormal Er04
3 Source A frequency abnormal Er05
4 Source B frequency abnormal Er06
5 Output Over Load Er16
6 Unit fault (Source A circuit power defected) Er22
7 Unit fault (Source B circuit power defected) Er23
8 Cabinet temperature abnormal Er24
9 Unit fault (Sensor circuit defect) Er25
10 Unit fault (EEPROM data abnormal) Er26
11 LCD panel connection abnormal Er28
12 Overload time out Er30
13 Transferring fail by sync setting condition Er31
14 Pre-alarm active Er32
15 Communication connection abnormal Er33
16 General alarm