EasyManua.ls Logo

Sungrow SG2500U-MV - Running Parameters

Sungrow SG2500U-MV
103 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System Manual 9 LCD Menu Operation
59
Two parameters pertinent to RS485 serial port communication can be set according to the
parameter range shown on the display.
“Address is prescribed by the plant staff and the address for each device must be unique
when there is more than one device. Baudis selected according to the communication
method adopted on-site.
Network Parameter Setting
Click Network Parameter to enter the following interface.
Six parameters pertinent to the Network communication can be set. DNS address 1 and
DNS address 2 can be set to the default value. Other parameters are assigned by plant
staff.
Set parameter with the aid of the pop-up keypad.
9.13.2 Running Parameters
Setting Running Parameters
Step 1 Tap “Function” from the default menu;
Step 2 Tap “Set-parameter”;
Step 3 Tap “Run-parameter” after entering the correct password.
Step 4 Set the running parameter by tapping the pop-up keypad and tap ENTER to confirm the
setting. Tap “Prev” or “Next” to turn pages up or down.

Table of Contents

Related product manuals