Annex10—3
10.7Menudrawingofthemenutoguidetheuser
Drawingofthemenuappearsfromsection12
10.8Thestartdispla y
Thestartpictureshownwhenthepotentiometerhasnotbeenactivatedfor10minutes
In:nnn%showsthecapacityorderedbythemainairhandlingunitcontroller.
Out:nnn%showsthecapacityorderedbythisinternalcontroller‐LMC251ofthecompressor.
10.9Settings
AboutbasicsettingsinthesubmenusintheLMC251
10.10Automaticresetsofthehighpressure switch
Thisisaboutthemaximumnumberofautomaticresetsofthehighpressureswitchthatareacceptable
withinonehour.Ifthisnumberisexceeded,theunitwillbeshutdownuntilthehighpressureswitchhas
beenresetmanually.
10.11Polarity
TheAlarmpolaritycanbesetto”NormallyOpen or”NormallyClosed”.
10.12Hotgassettingofperiod
Thisisthenumberofsecondsthatthehotgasvalveisopen.Theperiodisrelativelylong,butthesupply
temperatureisnotoscillatingatallandthestabilityofthesupplytemperatureissufficient.Thenumberof
secondsisafactorysettingthatshouldnotbereduced.Reductionofthe
numberofsecondswillnot
improvethestabilityofthetemperaturetoadegreethatcanbeprovenbymeasurements.Ifthenumber
ofsecondsisreduced,thenumberoftimesthatthevalveisopenedandclosedwillbeincreasedmaybe
considerably,andthevalvecouldbeworn
outprematurely.
10.13Limiter
DeltaMaxisthemaximumacceptablechangein%/secondoftheactualcoolingcapacity.
10.14Service
Inthismenuinformationaboutthesoftwareversioninthecontrolleraswellas2submenus“Manual
operation”and“Runtime”
10.15Manualoperation
WhenthemenuManualoperation‐isactivated,thetechnicianisabletocontroltheoperationmanually,
whenthestartsignalfromthemainairhandlingunitcontrollerison(startsignalisjustpotentialfree
connectionofthetwoterminals3&4).Thisprocedureisrelevantforthetestduring
theannual
maintenancewiththecontrolofallsafetyandregulationproceduresorafterinstallationofnew
components.
Ifnonewsettingshavebeencarriedoutonthecontrollerfor10minutes,themenuManualoperation
isdeactivated,andtheunitreturnstotheautomaticmode.
10.16Runninghoursandhotgasactivations
Inthismenuthenumberofrunninghoursforthecompressor,andthenumberofactivationsofthehotgas
valvecanberead.Thisinformationisvaluableforthemaintenance.
10.17Alarm
10.17.1Alarm
Showtheactualalarmwithalarmnumber.

Table of Contents

Other manuals for SystemAir Danvent DV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir Danvent DV and is the answer not in the manual?

SystemAir Danvent DV Specifications

General IconGeneral
BrandSystemAir
ModelDanvent DV
CategoryAir Handlers
LanguageEnglish

Related product manuals