Annex12—4
12.3AC‐fanoperationwithout thermistorforDanfossFC101.
Systemairfactoryset‐upisbasedonDanfossinitialization.
14‐22:Operationmode: [2]Initialisation(DanfossInitialisation)
Turnpoweroffandon.
Systemairfactoryset‐up:
0‐01:Languageselection:
1‐03:Torquecharacteristic:
[3]Auto‐Energyoptim.
1‐20:Motorpower: Accordingtomotorplate
1‐24:MotorCurrent: Accordingtomotorplate
1‐25:MotorNominalSpeed: Accordingtomotorplate
1‐29:Automaticmotoradption(AMA): [1]Kompl.motoradaptionto(Turnpoweroffandon.)
1‐42:MotorCableLeng th:
Orderspecific
1‐50:
MotorMagnetisationatzerospeed.: 0%
1‐52:Min.SpeedNormalMagnetisation: 10Hz
1‐73:Flyingstart: [0]Deaktivated
5‐40.0:FunctionRelay: [3]Driveready/remote
14‐03:Overmodulation: [1]Active
14‐20:ResetMode: [2]Automaticresetx2
0‐50:LCPCopy: [1]AlltoLCP(CopyofSystemairfactorysettingstopanel)
Connections:
0‐10V: terminal54‐55
Start: terminal12‐18
Driveready: terminal1‐2
Jumper terminal12‐27