Technical data |
31
15.5 Technical data tables
Table 4 SR/TR20-25
Power supply
Prefuse (A)
Fan fuse (A)
Heater fuse (A)
Total current consumption (A)
Total power consumption (kW)
Total power heater (kW)
Current power consumption fans (A/Unit)
Current consumption heater (A)
Power consumptions fans (kW/Unit)
SR/TR20 HWL, HWH, N
1~230 V+N +PE, 50Hz
13 C10
11,4 4,78 3,57 0,78
SR/TR 20 EL 5,2
3~400V+N +PE, 50Hz
20 C10 B32
14,64 9,98 5,2 3,57 7,5 0,78
SR/TR 20 EL 5,2 3~230V
3~230 V+PE, 50Hz
25 C10 B32
20,24 9,98 13,1 3,57 13,1 0,78
SR/TR20 HWL , HWH, N -MO
1-230 V+N +PE, 50Hz
13 C10
11,14 4,8 3,57 0,8
SR/TR 20 EL 5,2 -MO
3~400V+N +PE, 50Hz
20 C10 B32
14,64
10
5,2 3,57 7,5 0,8
SR /TR 25 HWL, HWH, N
1~230V +PE, 50Hz
13 C10
11,14 4,7 8 3,57 0,78
SR/TR 25 EL 5,2
3~400V+N +PE, 50Hz
20 C10 B32
14,64 9,98 5,2 3,57 7,5 0,8
SR/TR 25 EL 5,2 3~230V
3~230 V+PE, 50Hz
25 C10 B32
20,24 9,98 5,2 3,57 13,1 0,78
SR /TR 25 HWL, HWH, N -MO
1~230V +PE, 50Hz
13 C10
11,14 4,8 3,57 0,8
SR/TR 25 EL5,2 -MO
3~400V+N +PE, 50Hz
20 C10 B32
14,64
10
5,2 3,57 7,5 0,8
SR/TR35 HWL, HWH, N
1-230 V +PE, 50Hz
20 C16
15,8 5,3 5,9 1,3
SR/TR 35 EL 3,5
3~400V+N +PE, 50Hz
20 C16 B32
16,9 8,8 3,5 5,9 5,1 1,3
SR/TR 35 EL 7,1
3~400V+N +PE, 50Hz
32 C16 B32 22
12,4 7,1 5,9 10,2 1,3
SR/TR 35 EL 3,5 3~230V 3~230 V+PE, 50Hz
25 C16 B32
11,8 8,8 3,5 5,9 5,1 1,3
SR/TR 35 EL 7,1 3~230V
3~230 V+PE, 50Hz
35 C16 B32
18,4 12,4 7,1 5,9 17,8 1,3
Table 5 400V
Power supply
Prefuse (A)
Fan fuse (A)
Heater fuse (A)
Total current consumption (A)
Total power consumption (kW)
Total power heater (kW)
Current power consumption fans (A/Unit)
Current consumption heater (A)
Power consumptions fans (kW/Unit)
SR/TR35 HWL , HWH, N MO
3~400 V+N +PE, 50Hz 13 C10 11,4 5,8 3,8 2,5
SR/TR35 EL 3,5 MO
3~400V+N +PE, 50 Hz 20 C10 B32 15 6,5 3,5 3,8 5,1 2,5
SR/TR35 EL 7,1 MO
3~400V +PE, 50Hz 25 C10 B32 20 10,1 7,1 3,8 10,2 2,5
SR/TR60 HWL , HWH, N
3~400 V+N +PE, 50Hz 13 C10 10,6 7,9 3,5 2,1
SR/TR60 EL 3,5
3~400V+N +PE, 50 Hz 16 C10 B32 14,2 9,9 3,5 3,5 5,1 2,1
SR/TR60 EL 7,1
3~400V+N +PE, 50 Hz 25 C10 B32 19,3 13,5 7,1 3,5 10,2 2,1
SR/TR60 EL 10,4
3~400V+N +PE, 50 Hz 32 C10 B32 24,2 16,8 10,4 3,5 15,1 2,1
SR/TR60 HWL , HWH, N MO
3~400V+N +PE, 50 Hz 13 C10 10 6,1 3,2 2
SR/TR60 EL 3,5 MO
3~400V+N +PE, 50 Hz 16 C10 B32 13,6 9,6 3,5 3,2 5,1 2
SR/TR60 EL 7,1 MO
3~400V+N +PE , 50 Hz 25 C10 B32 18,7 13,2 7,1 3,2 10,2 2
SR/TR70 HWL, HWH, N
3~400 V +PE, 50Hz 13 C10 10,6 7,9 3,5 2,1