6.5 Programmable RAMP / SOAK (Only available for uPC model)
*For detail of the programmable instruction, please refer with page 25.
Press key
to display SV_1
Set SV_1 to 200.0
Set TM_1 to 01.00
(1 hour)
Set OUT1 to 100.0
SET
Assume the temperature profile is as below (use total 4 segments )
TIME
SV
RAMP SOAK
RAMP SOAK
1 hour
30
minutes
50
minutes
1 hour and
20 minutes
200
120
Set SV_2 to 200.0
Set TM_2 to 00.30
(30 minutes)
Set OUT2 to 100.0
Set SV_3 to 120.0
Set TM_3 to 00.50
(50 minutes)
Set OUT3 to 100.0
Set SV_4 to 120.0 Set TM_4 to 01.20
(1 hour and 20 minutes)
Set OUT4 to 100.0
Press key
to run program
(PRO LED start lighting)
Please operate conroller as following steps: