14.2 Calibration
SET 2.2 = 1
ANL1=0
ANH1=5000
LSPL=0
USPL=5000
Adjusts "ANL1" until PV Display = 0
Inputs 4mA
Inputs 20mA
Adjusts "ANH1" until PV Display = 5000
Inputs 4mA to CHECK LOW
Inputs 20mA to CHECK HIGH
OK ?
Set the range you want
LOW =LSPL HIGH =USPL
ExLow = -20.0High = 50.0
SET LSPL = -20.0USPL = 50.0DP000.0
To display ANL1 &
ANH1
at INPUT Level
Return User Level to view
the changing of PV
YES
NO