31
11. Heater Break Alarm (HBA)
11.1 HBA Wiring Example
SSR
+
-
AC POWER
CT
Heater
Sensor
OUT1
AL1
(HBA Relay)
(CT Input)
(Sensor Input)
11.2 HBA Function Description
HBA function detects the AC current flowing through the heater by a Current Transformer
(CT), and compares the CT input value and HBA set value. When OUT1 is ON and CT
input value is less than HBA set value during 5 seconds , AL1 is activated. Otherwise, AL1
is not activated.
The AC current flowing through heater can also be monitored in HBA setting mode.