21
Set
Set
Set
Set
Set
Full run time of proportional motor
Used for programmable controller
to wait continued operation
PV Filter
The same with CLO1
Range:5~200 seconds
0=Not wait
Others=Wait value
Set
Retransmission low limit calibration
Return to “INP1"
Output 2 low limit calibration
(Used for mA and V output)
Output 2 high limit calibration
(Used for mA and V output)
The same with CHO1
The same with CLO1
The same with CHO1
Retransmission high limit calibration
( Used for proportional motor valve
control output)
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Control mode
Heat / Cool
Control algorithm
PID / Fuzzy
Frequency
50 / 60HZ
ID number
Baudrate
SV compensation
PV compensation
Unit of PV & SV
Range:0 ~ 255
2400 / 4800 / 9600 /
19200 / 38400 bps
Range:-1000~1000
Range:-100.0~500.0
C(℃) / F(℉) / A(Analog)
Reserved
Set
Set
Set
Communication Protocol Selection
Communication Bits Configuration
MODBUS RTU /
MODBUS ASCII /
TAIE
O_81 /O_82/E_81/
E_82
PV will responese faster if
PVFT is smaller.