Display: Start threshold at the T.dem. sensor
Start differential for T.dem. set
Shutdown differential for T.dem. set
Display: Limit value for the minimum generator temperature
Start differential for T.gen. min.
Stop differential for T.gen. min.
➢ Starting demand by one sensor and stopping it by another is called using a holding circuit.
Start threshold = Set demand temperature + Diff. on at the T.dem. sensor
Shutdown threshold = Set shutdown temperature + Diff. off at the T.off sensor
➢ For a control function with start and shutdown thresholds on just one sensor, the Shutdown
temperature input variable must be set to unused. Set demand temperature thereby
receives a start differential and a stop differential alongside its threshold value:
Start threshold = Set demand temperature + Diff. on
Shutdown threshold = Set demand temperature + Diff. off
➢ A maximum temperature can be specified using the low end temperature T.dem. max. If
the set temperature for demand or shutdown is above that value, the low end temperature
is applied as the threshold value.
The low end temperature is only effective if the relevant set value is < 50 °C.
➢ If the generator temperature (cooling device temperature) falls below the value T.gen. min. +
Diff. off, demand will not be permitted and will be switched off even if the minimum runtime
has not yet expired.
Demand will not be re-enabled until the temperature exceeds T.gen. min. + Diff. on. The
minimum runtime counter will then restart.