EasyManua.ls Logo

Technische Alternative UVR 16x2 User Manual

Technische Alternative UVR 16x2
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
Cooling demand
30
Parameters
Demand temperature
T.dem. set
Diff. on
Diff. off (shown only if the
T.off sensor is not
defined)
Display: Start threshold at the T.dem. sensor
Start differential for T.dem. set
Shutdown differential for T.dem. set
Shutdown temperature
(shown only if the T.off
sensor is defined)
T.off set
Diff. off
Display: Shutdown threshold at the T.off sensor
Shutdown differential for T.off set
Low end temperature
T.dem. max.
Cooling demand starts if the T.dem. sensor captures a higher value
(only effective if T.dem. set < +50 °C)
Generator temperature
(shown only if the T.gen.
sensor is defined)
T.gen. min.
Diff. on
Diff. off
Display: Limit value for the minimum generator temperature
Start differential for T.gen. min.
Stop differential for T.gen. min.
Minimum runtime
Generator
Specifies the minimum ON time
Starting demand by one sensor and stopping it by another is called using a holding circuit.
Start threshold = Set demand temperature + Diff. on at the T.dem. sensor
Shutdown threshold = Set shutdown temperature + Diff. off at the T.off sensor
For a control function with start and shutdown thresholds on just one sensor, the Shutdown
temperature input variable must be set to unused. Set demand temperature thereby
receives a start differential and a stop differential alongside its threshold value:
Start threshold = Set demand temperature + Diff. on
Shutdown threshold = Set demand temperature + Diff. off
A maximum temperature can be specified using the low end temperature T.dem. max. If
the set temperature for demand or shutdown is above that value, the low end temperature
is applied as the threshold value.
The low end temperature is only effective if the relevant set value is < 50 °C.
If the generator temperature (cooling device temperature) falls below the value T.gen. min. +
Diff. off, demand will not be permitted and will be switched off even if the minimum runtime
has not yet expired.
Demand will not be re-enabled until the temperature exceeds T.gen. min. + Diff. on. The
minimum runtime counter will then restart.
Question and Answer IconNeed help?

Do you have a question about the Technische Alternative UVR 16x2 and is the answer not in the manual?

Technische Alternative UVR 16x2 Specifications

General IconGeneral
Data loggingYes, internal memory
WeightApprox. 300 g
Input Voltage24 V DC
DisplayLCD, 2x16 characters
Communication InterfacesCAN
Dimensions144 x 90 x 59 mm

Summary

General Information

Core Concepts

Input Variables

Explains the link between sensors and function inputs for data.

Parameters and Settings

Hystereses

Adjustable start and stop differentials creating switching hysteresis for control.

Analogue Function

Calculation Parameters

Settings for calculations like minimum, maximum, average, sum, and filter.

Multiplexer and Demultiplexer Parameters

Configuration for selecting input variables and routing output values.

Heating Demand

Cooling Demand

DHW Demand

Shading Function

Individual Room Control

Heating Circuit Control

Blind Control

Cascade

Cooling Circuit Control

Pasteurisation Function

Message Function

Mixer Control

PID Control

P-I-D Values and Parameters

Explains proportional, integral, and derivative components for system control.

Profile Function

Time Switch

Scaling Function

Solar Cooling

Solar Control

Solar Start / Drainback

Timer Function

Heat Meter

Maintenance Function

Conservatory Function

Input Variables and Parameters

Manages window ventilation based on room temp, wind, or rain sensors.

Meter / Counter

DHW Circulation

Input Variables and Parameters

Manages DHW circulation pump based on time, pulse, or mixing protection.

Related product manuals