Cooling demand
29
Cooling demand
Cooling demand starts when the demand temperature T.dem. exceeds the Set demand
temperature and stops when the shutdown temperature T.off falls below the Set shutdown
temperature.
If the T.off sensor is not used, both demand and shutdown are triggered via the T.dem. sensor.
An optional minimum temperature can be specified for cooling device A (the generator).
General enabling of the function (digital value ON/OFF)
Analogue input signal for the demand temperature
Analogue input signal for the shutdown temperature
Analogue value specifying the set demand temperature
Analogue value specifying the set shutdown temperature
Analogue input signal for the temperature of the heat generator
Analogue value specifying the minimum temperature of the generator
➢ If you want the set temperatures for demand, shutdown and minimum generator
temperature to be user-defined settings (fixed thermostat thresholds), specify User as the
source and enter the required value.