Heating demand
28
Output variables
Demand
Demand status ON/OFF; selection of the output
T.dem. < T.dem. set
Status ON if the demand temperature T.dem. is lower than the set
temperature T.dem. set + Diff. on.
T.off < T.off set
Status ON if the shutdown temperature T.off is lower than the set
temperature T.off set + Diff. off.
Low end temp. effective
Status ON if the set demand value falls below the low end
temperature T.dem. min., regardless of the demand status.
Minimum runtime ctr
Display of the remaining runtime for the minimum runtime, in seconds
T.gen. < T.gen. max.
Status ON if the boiler temperature is lower than the maximum
temperature T.gen. max. + Diff. off.
Effective set temperature
Display of the set temperature currently in use. If the heating demand
is not active, the output is 5 °C.
If there is no shutdown sensor, the output variable T.off < T.off set is switched by means of
the threshold T.dem. set + Diff. off.
If there is no generator sensor, the output variable T.gen. < T.gen. max. is always set to
status ON.