EasyManuals Logo
Home>Technische Alternative>Controller>UVR 16x2

Technische Alternative UVR 16x2 User Manual

Technische Alternative UVR 16x2
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
Heating demand
27
Parameters
Demand temperature
T.dem. set
Diff.on
Diff. off (shown only if the
T.off sensor is not
defined)
Display: Start threshold at the T.dem. sensor
Start differential for T.dem. set
Stop differential for T.dem. set
Shutdown temperature
(shown only if the T.off
sensor is defined)
T.off set
Diff. off
Display: Shutdown threshold at the T.off sensor
Stop differential for T.off set
Low end temperature
T.dem. min.
Heating demand if the demand temperature "T.dem. set" or shutdown
temperature "T.off set" falls below this value (only effective if T.dem.
set > +5 °C)
Generator temperature
(shown only if the T.gen.
sensor is defined)
T.gen. max.
Diff. on
Diff. off
Display: Limit value for the maximum generator temperature
Start differential for T.gen. max.
Stop differential for T.gen. max.
Minimum runtime
Generator
Specifies the minimum ON time
Starting the burner by demand from one sensor and shutting it down by another is called
using a holding circuit.
Start threshold = Set demand temperature + Diff. on at the T.dem. sensor
Shutdown threshold = Set shutdown temperature + Diff. off at the T.off sensor
For a control function with start and shutdown thresholds on just one sensor, the Shutdown
temperature input variable must be set to unused. If the boiler sensor is entered instead of
the cylinder sensor, the result is modulating boiler operation. Set demand temperature
thereby receives a start differential and a stop differential alongside its threshold value:
Start threshold = Set demand temperature + Diff. on
Shutdown threshold = Set demand temperature + Diff. off
A minimum temperature can be specified using the low end temperature T.dem. min.
If the set temperature for demand or shutdown is below that value, the low end temperature
is applied as the threshold value.
The low end temperature is only effective if the relevant set temperature is > 5 °C.
A value > 30 °C is only useful if the function is being used for modulating boiler operation. In
that case, the start and shutdown thresholds apply to the T.dem. sensor.
If the generator temperature (boiler temperature) exceeds the value T.gen. max. + Diff. off,
demand will not be permitted and will be switched off even if the minimum runtime has not
yet finished.
Demand will not be re-enabled until the temperature falls below T.gen. max. + Diff. on. The
minimum runtime counter will then restart.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Technische Alternative UVR 16x2 and is the answer not in the manual?

Technische Alternative UVR 16x2 Specifications

General IconGeneral
BrandTechnische Alternative
ModelUVR 16x2
CategoryController
LanguageEnglish

Related product manuals