SPECIFICATIONS
TMC7 Series
Page 4
710-02887-00A
Specifications
3.1 Current Ratings
AC53b 4-6:354
<1000 metres
AC53b 4-20:340
<1000 metres
40
o
C 50
o
C 40
o
C 50
o
C
TMC7-007 18 A 17 A 17 A 15 A
TMC7-015 34 A 32 A 30 A 28 A
TMC7-018 42 A 40 A 36 A 33 A
TMC7-022 48 A 44 A 40 A 36 A
TMC7-030 60 A 55 A 49 A 45 A
AC53b 4-6:354
<1000 metres
AC53b 4-20:340
<1000 metres
TMC7-037 75 A 68 A 65 A 59 A
TMC7-045 85 A 78 A 73 A 67 A
TMC7-055 100 A 100 A 96 A 87 A
TMC7-075 140 A 133 A 120 A 110 A
TMC7-090 170 A 157 A 142 A 130 A
TMC7-110 200 A 186 A 165 A 152 A
AC53b Utilisation Category Format
90 A: AC-53b 3.5-15 : 345
Starter Current Rating
(amperes)
Start Current
(multiple of FLC)
Start Time
(seconds)
Off Time
(seconds)
Starter Current Rating: The Full Load Current rating of the soft starter given the parameters detailed in the remaining sections of the
utilisation code.
Start Current: The maximum available start current given the parameters detailed in the remaining sections of the utilisation
code.
Start Time: The maximum available start time given the parameters detailed in the remaining sections of the utilisation
code.
Off Time: The minimum allowable time between the end of one start and the beginning of the next start given the
parameters detailed in the remaining sections of the utilisation code.
Contact your local supplier for ratings under operating conditions not covered by the above ratings charts.