CG-SVX027E-GB
3
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
General Information
Foreword
These instructions are given as a guide to good practice
in the installation, start-up, operation, and maintenance
by the user, of Trane CGAX chillers or CXAX heat
pumps. They do not contain full service procedures
necessary for the continued successful operation of this
equipment.
The services of a qualied technician should be
employed through the medium of a maintenance
contract with a reputable service company. Read this
manual thoroughly before unit start-up.
A separate manual is available for the use and
maintenance of the unit’s control, Tracer™ Symbio800.
Units are assembled, pressure tested, dehydrated,
charged and tested in accordance with factory standard
before shipment.
Warnings and cautions
Warnings and Cautions appear at appropriate sections
throughout this manual. Your personal safety and the
proper operation of this machine require that you follow
them carefully. The constructor assumes no liability
for installations or servicing performed by unqualied
personnel.
WARNING!: Indicates a potentially hazardous situation
which, if not avoided, could result in death or serious
injury.
CAUTION!: Indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It may also be used to alert against unsafe
practices or for equipment or property-damage only
accidents.
CAUTION!: Time before to work on the electrical panel
of the unit with Low Ambient option: once the unit is
off (conrmed by the extinction of the display), it is
mandatory to wait ve minutes before working on the
electrical panel.
Safety recommendations
To avoid death, injury, equipment or property damage,
the following recommendations should be observed
during maintenance and service visits:
1. The maximum allowable pressures for system leak
testing on low and high pressure side are given
in the chapter “Installation”. Do not exceed test
pressure by using an appropriate device.
2. Disconnect the main power supply before any
servicing on the unit.
3. Service work on the refrigeration system and the
electrical system should be carried out only by
qualied and experienced personnel.
4. Refer Addendum (PROD-SVX01) to Manuals for
units with refrigerant, for conformity to the Pressure
Equipment Directive (PED) 2014/68/EU, Machinery
Directive 2006/42/EC, and safety recommendations.
Reception
On arrival, inspect the unit before signing the delivery
note. Specify any visible damage on the delivery note,
and send a registered letter of protest to the last carrier
of the goods within 7 days of delivery.
Notify the local TRANE sales ofce at the same
time. The delivery note must be clearly signed and
countersigned by the driver.
Any concealed damage shall be notied by a registered
letter of protest to the last carrier of the goods within
7 days of delivery. Notify the local TRANE sales ofce
at the same time.
Important notice: No shipping claims will be accepted
by TRANE if the above mentioned procedure is not
respected.
For more information, refer to the general sales
conditions of your local TRANE sales ofce.
Note: Unit inspection in France.
Delay to send registered letter in case of visible and
concealed damage is only 72 hours.
Warranty
Warranty is based on the general terms and conditions
of the manufacturer. The warranty is void if the
equipment is repaired or modied without the written
approval of the manufacturer, if the operating limits are
exceeded or if the control system or the electrical wiring
is modied. Damage due to misuse, lack of maintenance
or failure to comply with the manufacturer’s instructions
or recommendations is not covered by the warranty
obligation. If the user does not conform to the rules of
this manual, it may entail cancellation of warranty and
liabilities by the manufacturer.