CG-SVX027E-GB
41
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
Controls/Tracer TD7 Operator Interface
Controls Overview
Conquest CGAX / CXAX units use the following control/
interface components:
Tracer™UC800/Symbio800 Controller
Tracer TD7 Operator Interface
Communication Interfaces
There are four connections on the Tracer™UC800/
Symbio800 that support the communication interface :
BACnet MS/TP
BACnet IP (Only with Symbio800)
MODBUS RTU
MODBUS TCP (Only with Symbio800)
Tracer TD7 Operator Interface
Operator Interface
Information is tailored to operators, service technicians
and owners. When operating a chiller, there is specic
information you need on a day-to-day basis, like set
points, limits, diagnostic information, and reports.
Day-to-day operational information is presented at the
display. Logically organized groups of information-chiller
mode of operation, active diagnostics, settings and
reports put information conveniently at your ngertips.
Tracer™ TU
The TD7 operator interface allows for daily operation
tasks and set point changes. However to adequately
service Conquest CGAX chillers / CXAX Heat Pump,
Tracer™TU service tool is required (Non-Trane
personnel, contact your local Trane ofce for software
purchase information). Tracer TU adds a level of
sophistication that improves service technician
effectiveness and minimizes chiller downtime. This
portable PC-based service-tool software supports service
and maintenance tasks