CG-SVX027E-GB
46
4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Operation
Control System
Unit operation is intergrally managed by the
microprocessor-based unit Tracer™ Symbio 800
controller.
Unit Operation
• Check that the chilled water pump(s) operates correctly
• Start up the unit following procedure described in
the unit controller user guide. The unit will operate
correctly when there is sufcient water ow. The
compressors will start up if the evaporator water
leaving temperature is above the control module
setpoint.
Weekly start up
• Check that the chilled water pump(s) operates correctly
• Start up the unit following procedure described in the
unit controller user guide
Weekend shutdown
• If the unit needs to be shut down for a short period of
time, stop the unit following procedure described in
the unit controller user guide. (See «Clock» menu)
• If the unit is shut down for a longer period, see under
«Seasonal shutdown», below
• Ensure that all safeties are taken to prevent frost
damages during negative ambient temperature
• Do not put the general disconnect switches to
off, except if the unit is drained. Trane does not
recommend draining the unit, due to the fact that it
increases corrosion
Seasonal shutdown
• Check water ows and interlocks
• Check glycol % in the chilled water circuit if glycol
presence is required
• Carry out leak test
• Carry out oil analysis
• Record operating pressures, temperatures, amperages
and voltage
• Check operation of machines/ compare conditions of
operation against original commissioning data
• Stop the unit following procedure described on the
unit controller user guide
• Ensure that all safeties are taken to prevent frost
damages during negative ambient temperature
• Fill out the visit log sheet and review with the
operator - Do not put the general disconnect switch to
off, except if the unit is drained
• Trane does not recommend draining the unit, due to
the fact that it increases corrosion
Seasonal start-up
• Check water ows and interlocks
• Check Ethylene glycol % in the chilled water circuit if
glycol presence is required
• Check operational setpoints and performance
• Calibrate controls
• Check operation of all safety devices
• Inspect contacts and tighten terminals.
• Megger the motor compressor windings
• Record operating pressures, temperatures, amperages
and voltage
• Carry out leak test
• Check conguration of unit control module
• Change the oil as required based upon results of the
oil analysis made during seasonal shutdown Get the
8 condition measurements at the same time, on each
circuit
• H P
• L P
• Suction temperature
• Discharge temperature
• Liquid temperature
• Water entering temperature
• Water leaving temperature
• Outdoor ambient temperature Then calculate the sub-
cooling and superheat. No diagnosis can be accurate
with one of these recordsmissing
• Check operation of machines/compare conditions of
operation against original commissioning data
• Fill out the visit log sheet and review with the operator