EasyManuals Logo
Home>Trane>Air Handlers>CSAA

Trane CSAA User Manual

Trane CSAA
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #97 background imageLoading...
Page #97 background image
Component Installation
CLCH-SVX07K-EN 97
Discharge Plenum Connections
Discharge plenum sections are available with or without
openings. Sections with rectangular and round openings
have a framed opening that can be used to secure the duct
to the frames. If the duct is lined, it is important the
insulation does not obstruct the opening of the section.
For a discharge plenum with field-cut openings, attach the
duct to the side panel.
Figure 122. Field-supplied duct connection to AHU bottom supply/return air opening
Bottom supply/
return airflow
Field-supplied
rigid duct
Field-supplied
rigid duct
Typical Trane
air handler base
Typical Trane
air handler base
Figure 123. Field-supplied duct connection details - curb
mount for outdoor units
Field-supplied
duct
Gasket
Supply opening
in floor
Roof curb
Unit wall
Unit floor
Building roofing and
structure may vary per job
Unit base
3-50-14 ga
57-120-10 ga
3-120-10 ga
6 inches
1 in. flange
3-120-16 ga
Figure 124. Field-supplied duct connection details - pier
mount for outdoor units
Gasket
Supply opening
in floor
Unit wall
Unit floor
Building roofing and
structure may vary per job
Unit base
3-50 - 3 inches
57-120 - 4 inches
1 in. flange
Field-supplied
duct

Table of Contents

Other manuals for Trane CSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane CSAA and is the answer not in the manual?

Trane CSAA Specifications

General IconGeneral
BrandTrane
ModelCSAA
CategoryAir Handlers
LanguageEnglish

Related product manuals