Unit Start Up
102 RT-SVX36K-EN
&Troubleshooting Guide (RT-SVP07*-EN) to get to the
appropriate HI menu and make proper selections.
To make fan speed adjustments as required by the
application:
1. Through the Human Interface, select Setup Menu.
2. Once in the Setup Menu, navigate to Device
Characteristics Setup Definitions screen. Press Enter.
3. Navigate to Actuator Setup Supply Fan IGV/VFD Cmd
Min and Max Voltage screens.
4. Change the Min and Max Voltage settings as shown in
Table 39 to adjust fan speed modulating range:
Note: Maximum operating speed cannot exceed fan
wheel mechanical limit.
System Airflow Measurements
Constant Volume Systems
1. Ensure that the “System” selection switch at the
remote panel is in the Off” position and the “Fan”
selection switch for constant volume units is in the
Auto” position. (VAV units do not utilize a “Fan
selection input.)
2. Close the disconnect switch or circuit protector switch
that provides the supply power to the unit's terminal
block 1TB1 or the unit mounted disconnect switch
1S14.
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK
1TB1 OR UNIT DISCONNECT SWITCH 1S14.
3. Turn the 115 volt control circuit switch 1S1 and the 24
volt control circuit switch 1S70 to the On” position.
4. Open the Human Interface access door, located in the
unit control panel, and press the SERVICE MODE key to
display the first service screen. Refer to the latest
edition of the appropriate programming manual for CV
or VAV applications for the SERVICETEST screens and
programming instructions.
Table 45. Voltage ranges for DDP supply fan speed
adjustments
Fan Speed
(RPM)
VFD Frequency
Range (Hz)
Actuator Setup
Supply Fan IGV/VFD
Cmd
Max Min Max Min Max Min
2400 888 83 31 10.0 2.4
2300 851 79 29 9.4 2.1
2200 814 76 28 9.0 1.9
2100 777 72 27 8.4 1.8
2000 740 69 26 7.9 1.6
1900 703 66 24 7.5 1.3
1800 666 62 23 6.9 1.2
1700 629 59 22 6.5 1.0
1600 592 83 31 10.0 2.4
1500 555 79 29 9.4 2.1
1400 518 74 27 8.7 1.8
1300 481 68 25 7.8 1.5
1200 444 63 23 7.1 1.2
1100 407 58 21 6.3 0.9
1000 370 53 20 5.6 0.7
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.

Table of Contents

Other manuals for Trane IntelliPak

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak and is the answer not in the manual?

Trane IntelliPak Specifications

General IconGeneral
BrandTrane
ModelIntelliPak
CategoryAir Conditioner
LanguageEnglish

Related product manuals