Unit Start Up
RT-SVX36K-EN 131
Pressure Curves
To Check Operating Pressures
1. Start the unit and allow the pressures to stabilize.
Note: If unit includes the Modulating Dehumidification
Control option, pressure curves apply to the
cooling mode only.
2. Measure the outdoor air dry bulb temperature (F)
entering the condenser coil.
3. Measure the discharge and suction pressure (psig)
next to the compressor.
4. Plot the outdoor dry bulb temperature and the
operating suction pressure (psig) onto the chart.
5. At the point of intersection, read to the left for the
discharge pressure.The measured discharge pressure
should be within ± 7 psig of the graph.