BAS-SVX078E-EN
19
Settings
Table 1. Group 1 standard settings
Menu Item Options [Default] Description
Cooling Type None [Cooling Only]/ Heat Pump Select the type of outdoor unit installed
Cooling Stages [Single Stage], Two Stage Select the number of outdoor unit stages.
Compressor Type
Single Compressor Two Stage,
[Two Compressor Two Stage]
Select the compressor type for multi-stage outdoor
units.
Heating Type [Gas/Oil], Electric, Hydronic Select the type of indoor unit installed.
Heat Stages [Single Stage], Two Stage, Three Stage Select the number of heat stages
Blower Type
Variable, [Non-Variable]
(a)
Select the blower type [Constant Torque motors are
considered non-variable speed]
(a)
SOV Operation
[with Cooling Call], with Heating Call Select which mode of operation energizes the
switch-over valve.
(a)
Variable speed applies only to supported Trane residential equipment
Table 2. Group 2 equipment settings
Menu Item Options [Default] Description
Compressor Cooling Cycles per Hour
2 to 6 Cph [3] Select the number of cycles per hour during cooling
operation.
1st Stage Compressor Cooling Cycles Per Hour
2 to 6 Cph [3] Select the cycles per hour during 1st stage cooling
operation
2nd Stage Compressor Cooling Cycles Per Hour
2 to 6 Cph [3] Select the number of cycles per hour during 2nd
stage cooling operation
Compressor Heating Cycles Per Hour
2 to 6 Cph [3] Select number of cycles per hour during
compressor heating operation.
1st Stage Compressor Heating Cycles Per Hour 2 to 6 Cph [3] Select the minimum runtime [MRT] of stage 1 heat
2nd Stage Compressor heating Cycles Per Hour 2 to 6 Cph [5] Select the minimum runtime [MRT] of stage 2 heat
Heating Cycles Per Hour
2 to 6 Cph [5] Select the number of cycles per hour during heat
operation
1st Stage Heat Cycles Per Hour
2 to 6 Cph [5] Select the number of cycles per hour during 1st
stage heat operation
2nd Stage Heat Cycles Per Hour
2 to 6 Cph [5] Select the number of cycles per hour during 2nd
stage heat operation
3rd Stage Heat Cycles Per Hour
2 to 6 Cph [5] Select the number of cycles per hour during 3rd
stage heat operation
System Setup